• AWWA SOURCES55634
Provide PDF Format

Learn More

AWWA SOURCES55634

  • X-Ray Machines: Converting From Pass-Through to Re-Circulating
  • Conference Proceeding by American Water Works Association, 01/01/2002
  • Publisher: AWWA

$12.00$24.00


Hospitals commonly have several medical x-ray processors operating 24 hours per day, 365 days per year. Published water flow rates for the 35 units on the market range from .2 to 2.5 gallons per minute (gpm), but can flow at much higher rates in practice. Units specified to operate at 2.5 gpm are very common while the .2 gpm units are rare. This study tested a new technology that re-circulates the water to the film processor thereby reducing consumption to approximately 35,000 gallons per year. The Los Angeles Department of Water and Power has had several customers install the equipment with the savings verified by a meters specifically placed to measure processor flows. To gain more precise information on the effect, Irvine Ranch Water District used a datalogger that continuously recorded the flow prior to and after the installation. In all cases, the equipment performed well and saved the anticipated amount of water. Includes table.

Related Products

AWWA JAW21569

AWWA JAW21569

Journal AWWA - Seattle's Experience With Distribution System Sampling ..

$15.00 $30.00

AWWA ACE54425

AWWA ACE54425

New Analytical Tools for Distribution System Surveillance..

$12.00 $24.00

AWWA ACE61695

AWWA ACE61695

Seattle Maximizes Its Security Investment with a Prudent, Yet Reasonable, Master Plan..

$12.00 $24.00

AWWA WQTC58914

AWWA WQTC58914

Managing Conversion to Chloramines..

$12.00 $24.00