• AWWA ACE61771
Provide PDF Format

Learn More

AWWA ACE61771

  • Galvanic Corrosion of Lead Bearing Plumbing Devices
  • Conference Proceeding by American Water Works Association, 06/17/2005
  • Publisher: AWWA

$12.00$24.00


This study reports on the increase of lead contamination of water contacting brass or lead bearing plumbing if there is a galvanic connection to copper. The rate at which lead materialswere sacrificed by galvanic action was directly influenced by various factors includingchloride and sulfate concentrations, type of disinfectant, pH and insulating gaps betweenthe metals. The galvanic current spatially separates the anodic and cathodic reactions,thereby lowering the pH near the surface of the lead materials in poorly buffered watersand increasing lead solubility. Chloramine caused sustained galvanic currents relative tochlorine. The partial replacement of lead service lines by new copper pipes can beexpected to increase lead leaching under at least some circumstances. Includes 20 references, figures.